Learn Type II evacuation levels, charging procedures for blends, weighing-in method, and nitrogen sweep before brazing.

6m read

Type II Evacuation Levels

For high-pressure equipment using post-November 15, 1993 recovery equipment: systems with less than 200 lbs of refrigerant must be evacuated to 0 psig, and systems with 200 lbs or more must be evacuated to 10 inches Hg vacuum. Proper evacuation removes moisture and non-condensable gases. A vacuum pump pulls the system below atmospheric pressure, lowering the boiling point of any trapped moisture so it vaporizes and is removed. Always use a micron gauge for precise vacuum measurement.

Post-1993 equipment: <200 lbs evacuate to 0 psig; >=200 lbs evacuate to 10 in. Hg vacuum.

Keep reading