Recovery Levels by Charge Size
For high-pressure equipment manufactured after November 15, 1993, the required evacuation level depends on the refrigerant charge size. Systems containing less than 200 pounds of refrigerant must be recovered to 0 psig. Systems containing 200 pounds or more must be recovered to 10 inches of mercury (Hg) vacuum. These levels ensure that the maximum practical amount of refrigerant is removed before opening a system for service.
Post-11/15/93 systems: less than 200 lbs recover to 0 psig; 200 lbs or more recover to 10 inches Hg vacuum.