Study Guide
Lesson 32/52Preview

Leak Detection & Repair

Understand leak rate thresholds, detection methods, and repair documentation requirements.

5m read

Leak Rate Thresholds

Leak repair requirements apply to ODS systems with 50+ lbs of refrigerant under Section 608, and as of January 1, 2026, to HFC systems with 15+ lbs under the AIM Act. The annual leak rate thresholds are the same for both: comfort cooling must repair leaks exceeding 10%, commercial refrigeration at 20%, and industrial process refrigeration at 30%. Residential and light commercial AC/heat pumps are exempt from HFC leak repair provisions. Leaks exceeding the threshold must be repaired within 30 days.

Leak thresholds: 10% comfort cooling, 20% commercial refrigeration, 30% industrial. Apply to ODS (50+ lbs) and HFCs (15+ lbs as of 2026).

Keep reading

This is a preview. Unlock every Type I, II, and III lesson for $14.99 once. No subscription.